  • Messaggio d'errore inverter AEG PV2800

    Buongiorno a tutti, utilizzando il programma di monitoraggio del mio inverter mi sono arrivati diversi messaggi di warning con la dicitura "The measure AC voltage is out of tolerable range". Avete idea se può essere un problema dell'impianto FV o è causato dalla rete di Enel? Grazie.
    Di seguito il report:

    Inverter Warning Report 2011/03/11 13:46:28

    Value
    Description
    Alias Name
    1009BJ0031
    Inverter alias name or serial number
    Temperature
    48.4
    oC: Inverter internal temperature
    Vpv1/2/3
    418.9/NA/NA
    V : PV voltage
    Ipv1/2/3
    NA/NA/NA
    A : PV current
    Ppv1/2/3
    NA/NA/NA
    W : PV Power
    Iac
    0.0
    A : Current to grid
    Vac
    252.5
    V : Grid voltage
    Fac
    50.05
    Hz : Grid frequency
    Pac
    0
    W : Power to grid
    Zac
    NA
    mOhm : Grid impedance
    E-Total
    187.4
    kWh : Total energy to grid
    E-Today
    0.00
    kWh : Today's energy to grid
    h-Total
    250
    Hr : Total Operation hours
    Mode
    Fault
    Operation Mode
    Error
    The measured AC voltage is out of tolerable range

  • #2
    Nessuno mi può aiutare?

    Commenta


    • #3
      Non conosco l'inverter....... ma sembra che misuri su ENEL 252,5 Volt e quindi dà errore di rete....
      E' quasi il 10% fuori dai 230 Volt.
      2,99 KWp - 13 Pannelli Winaico 230 Wp - Inverter AURORA PVI-3.0
      Az. 9° S-O - 35° - conn. 8/2/11 - 2° CE - Prod. 2011-15 1.483 - 1.395 - 1.246 - 1.212 - 1.284 KWh/KWp
      14,52 KWp - 66 Pannelli Sharp 220 Wp - Inverter KACO 16.0 TR3
      Az.26° S-O - 30° - conn. 6/5/11 - 3° CE - Prod. 1.475 - 1.392 - 1.267 KWh/KWp

      Commenta


      • #4
        Ciao Rob77, in realtà i volts misurati sono di più; di seguito ti riporto i messaggi d'errore riportati nella giornata del 19/3:

        Error time Recovery time Mode Error Message


        Error Value
        11/03/2019 10.44 11/03/2019 10.45 Fault Vac out of range (The measured AC voltage is out of tolerable range)


        Vac : 260.4 V
        11/03/2019 12.20 11/03/2019 12.21 Fault Vac out of range (The measured AC voltage is out of tolerable range)


        Vac : 260.4 V
        11/03/2019 12.21 11/03/2019 12.23 Fault Vac out of range (The measured AC voltage is out of tolerable range)


        Vac : 260.4 V
        11/03/2019 13.05 11/03/2019 13.06 Fault Vac out of range (The measured AC voltage is out of tolerable range)


        Vac : 260.4 V
        11/03/2019 13.07 11/03/2019 13.08 Fault Vac out of range (The measured AC voltage is out of tolerable range)


        Vac : 262.4 V
        11/03/2019 13.09 11/03/2019 13.10 Fault Vac out of range (The measured AC voltage is out of tolerable range)


        Vac : 260.4 V
        11/03/2019 13.10 11/03/2019 13.11 Fault Vac out of range (The measured AC voltage is out of tolerable range)


        Vac : 260.4 V
        11/03/2019 13.13 11/03/2019 13.15 Fault Vac out of range (The measured AC voltage is out of tolerable range)


        Vac : 262.4 V
        11/03/2019 13.16 11/03/2019 13.17 Fault Vac out of range (The measured AC voltage is out of tolerable range)


        Vac : 260.4 V
        11/03/2019 13.18 11/03/2019 13.19 Fault Vac out of range (The measured AC voltage is out of tolerable range)


        Vac : 260.4 V
        11/03/2019 13.20 11/03/2019 13.21 Fault Vac out of range (The measured AC voltage is out of tolerable range)


        Vac : 260.4 V
        11/03/2019 13.21 11/03/2019 13.22 Fault Vac out of range (The measured AC voltage is out of tolerable range)


        Vac : 260.4 V
        11/03/2019 13.23 11/03/2019 13.25 Fault Vac out of range (The measured AC voltage is out of tolerable range)


        Vac : 260.4 V
        11/03/2019 13.25 11/03/2019 13.29 Fault Vac out of range (The measured AC voltage is out of tolerable range)


        Vac : 260.4 V











































































        Commenta


        • #5
          Questo è proprio un problema sulla rete ENEL...... chiama il tuo installatore e fagli controllare la linea.
          2,99 KWp - 13 Pannelli Winaico 230 Wp - Inverter AURORA PVI-3.0
          Az. 9° S-O - 35° - conn. 8/2/11 - 2° CE - Prod. 2011-15 1.483 - 1.395 - 1.246 - 1.212 - 1.284 KWh/KWp
          14,52 KWp - 66 Pannelli Sharp 220 Wp - Inverter KACO 16.0 TR3
          Az.26° S-O - 30° - conn. 6/5/11 - 3° CE - Prod. 1.475 - 1.392 - 1.267 KWh/KWp

          Commenta


          • #6
            Grazie, chiederò lumi!

            Commenta